AUTOMATIC TRANSFER UNIT AUTOMATIC TRANSFER UNIT
EAS 5D
Our Price £ + vat

Programmable from front panel
Microprocessor based control unit
Setup protected by access code
Remote start/stop (normal or EJP)
 Alarms for engine and generator
Built in transfer switches
Automatic test at preset intervals
Programmable maintenance intervals

Standard equipment
EJP Function
Connection cable to generating set = 10m
Remote start/stop input
  Options on request
Voltage 230V, single-phase
Voltage 230V, three-phase
Warning siren

GENERAL SPECIFICATIONS

EAS 5   230v, 1-phase, 6 kva
     
EAS 5D
Standard
230v, 1-phase, 6 kva
    400v, 3-phase, 6 kva
 
Optional
230v, 3-phase, 6 kva
Frequency   50/60Hz
Protection   IP44
Dimensions   220 x 75 x 350
Weight   4 kg

CONTROL UNIT SPECIFICATIONS

Nominal supply voltage
Voltage variance
PCB current
Battery charger voltage
Charging current
IMin. and max temp.
12V dc
6.5-15V
100mA
13.8VDC
500mA
0-40°C

MAIN FEATURES
Control based on 11 Mhz Intel 80c552 microprocessor
32Kbyte EPROM memory program
32Kbyte static RAM data memory
256 word EEPROM involatile data memory
Three (3) figure LED display
Function/status/alarm visualization by means of 15 LED's
Diaphragm type push buttons with mechanical effect
Voltage measured at Real Effective Value (RMS)
All setups accessible from the front without dip switches (by software in permanent memory)
Setups protected by access code
Battery charger with "Intelligent" modulation of voltage and current

The LED's on the front panel indicate:
• ALARMS - ON alarms are active
• ENGINE ON engine running
• ST. FAILURE engine failed to start
• FAILURES a problem has occurred - see display for detail
• BATTERY battery is not being charged

The 3 digit display shows:
• Mains/generator voltage (VOLT)
• Generator frequency (HERTZ)
• Battery voltage (V. BATT.)
• Operating hours (HOUR METER)
• Code for alarms or maintenance

  The push buttons have these function:
• RESET reset the system after an alarm
• MAN. operate the system manually
• STOP stop the system when operating in manual mode
• START start the system when operating in manual mode
• AUT. system operates automatically
• TEST simulate an intervention
• MIS. select the signal to be displayed on meter

MOSA emergency power systems take over the supply of electrical power automatically in the event of mains failure or insufficiency. A complete system consists of the generating set, a control module and transfer contactor switches.

The MOSA EAS series of control units (EAS 5 – 110) combine the control module and the transfer contactor switches in a single housing, which can be mounted in any convenient location. They are not part of the generating set. They can be used with any MOSA generator with a model name ending in "EAS" from 4 kVA up.

The EAS control unit is programmable and can be set up to meet almost any requirement. It monitors the mains voltage and when it falls below a preset value it automatically starts the generator engine, monitors it and, when everything is OK, switches the load from the mains to the generator. When the mains comes back on it switches the load from the generator back to the mains, lets the engine cool down and shuts it down, ready for the next . It also can be remotely started either by a contact closure or with the EJP system, which is mainly used in France).

The control circuitry of the MOSA EAS - Automatic Mains Failure Control Panels is based on an Intel 80c552 Microprocessor working at 11 MHz. The program is stored in a 32 Kbyte EPROM while the data is stored in a 32 Kbyte RAM. A 256 Word EEPROM serves as a non-volatile memory. The EAS units are equipped with an Ammeter (not EAS5-5), three figure display, 15 LED's to indicate the functions, alarms and status, and 7 membrane-push buttons with a positive mechanical feel. All functions and values can be set from the front panel. A code is required to change certain settings to avoid changes made by unauthorized persons. A battery charger using intelligent modulation of current and voltage is included.

Our Price £650 + vat